Kurtyna dymowa T35KD

T35KD Smoke Curtain

T35KD smoke curtain made of S280GD galvanized sheet metal, 0.60 mm thick. The curtain is coated on both sides with a 15-micrometer-thick protective polyester coating.

Technical specification

Technical Information

Below you will find the key technical specifications of our T35KD smoke curtain. The curtain offers very high performance, which is confirmed by tests and certifications in accordance with the PN EN 12101-1 standard. The curtain is coated with polyester paint on both sides. If the attached documents do not contain all the necessary information, please contact our technical department, which will provide you with detailed answers to all your questions.


Curtain Type
SSB

Fire resistance
DHA
Maximum curtain flow rate
25m³/ha²
Maximum gap size
20 mm
Kurtyna dymowa T35KD - przekroj

Curtain Load

The load per 1 m of curtain, depending on its height, is shown in the table:

Curtain height [m] Load [kN/m]
0.50 0.028
1.00 0.055
1.50 0.083
2.00 0.110
2.50 0.138
3.00 0.165
3.50 0.193
4.00 0.220
4.50 0.248

Recommendations

Recommendations for Installing Smoke Curtains

T35KD fixed smoke curtains are secured along their upper edge to the support structure using self-tapping fasteners. The support structure must have the required fire resistance class, as determined by the building’s fire resistance class. The curtain is secured with at least two fasteners, and the metal sheets forming the curtain are fastened together using self-tapping fasteners.

The manufacturer’s technical requirements for assembly components are detailed in the T35KD assembly manual; however, the manufacturer permits the use of fasteners with fire resistance and mechanical properties that are at least as good as those recommended.

If the entire curtain is not rectangular in shape and the last sheet to be installed cannot be mounted in one piece, the sheets must be cut to size. Use electric shears with a rotating head to cut the sheets. After completing the assembly, be sure to clean the surface of any metal shavings, screws, etc. If the surface is damaged, make the necessary (spot) touch-ups as soon as possible using paint that matches the original color of the sheets. If a grinder is used, complaints will not be accepted.

NOTE: Regardless of the manufacturer’s installation recommendations, the facility designer is responsible for the design of the fasteners used to secure the curtain panels to the structure and for the design of the structure itself to which the curtain is to be attached. Pruszyński Company can provide support to designers in the form of technical consultations for a given project.

Methods for Installing Smoke Curtains

For T35KD smoke curtains manufactured by Blachy Pruszyński Company, assembly consists of two steps: welding the metal sheets together and attaching them to the structure.

NOTES

  • The support structure for smoke curtains must have the required fire resistance, as determined by the fire resistance class of the building in which it will be installed
  • When performing assembly of smoke curtains, use fasteners in accordance with the Classification Report (REPORT) and the assembly instructions (DOWNLOADS). Other fasteners with fire resistance and mechanical properties that are no less favorable may be used. The designer is responsible for the selection of fasteners.

You can find examples and detailed descriptions of curtain assembly, along with examples of use, in the assembly manual for the T35KD: DOWNLOADS

A) Joining metal sheets together

  1. Connect the metal sheets to each other using fasteners spaced 200 mm apart
  2. Fastener type: WSBP self-tapping fasteners manufactured by KLIMAS Sp. z o.o., dimensions: 4.8 x 19 mm, made of SAE1022 steel
  3. Method for installing fasteners according to the manufacturer’s specifications

​Note: The use of other fasteners with fire resistance and mechanical properties that are at least as good is permitted.

Joining the curtain panels together

B) Fastening Sheet Metal to Structures

  1. Secure the structural sheet metal with at least 2 fasteners in each fold.
  2. Fastener type: GT12 self-tapping fasteners manufactured by ETANCO Sp. z o.o., dimensions: 5.5 x 35 mm, made of SAE 1022 carbon steel
  3. Method for installing fasteners according to the manufacturer’s specifications
  4. 3

Fastening Sheet Metal to Structures

Delivery, Transportation, and Unloading

  • DELIVERY

T35KD fixed smoke curtains are supplied in the form of rectangular trapezoidal sheets with an effective width of 1.05 m and a length equal to the designed height of the curtain (up to 4.50 m). Sealing elements made of steel sheet, which provide a seal where the curtain sheet meets the trapezoidal sheet of the roof, as well as self-tapping fasteners for joining the curtain panels together, may also be supplied.

  • TRANSPORT

If you are picking up the goods with your own vehicle, the vehicle must have an open loading platform that allows for easy loading and unloading. Galvanized and aluzinc sheets must be protected from getting wet at all costs!

  • UNLOADING

“Manual” unloading should be performed by an adequate number of people—that is, enough to ensure that the panels are not shifted against one another, their side edges are not bent, and they are not stretched. Deformation of the panels during unloading and handling leads to subsequent problems with their proper assembly (gaps at the fasteners, which can cause the curtain to leak). The most appropriate method is to unload the panels in the manufacturer’s packaging using mechanical equipment.

Storage Recommendations

  • Sheets stored in bundles must not be kept outdoors or in areas exposed to moisture and fluctuating temperatures. Zinc and aluzinc coatings, particularly those that have not yet been exposed to the elements—and thus lack a protective layer—are sensitive to water condensation when air circulation is limited (sheets stored in stacks). Special attention should be paid to unloading in winter conditions and storage in heated warehouses. Due to significant temperature differences between the sheets, water condenses.
  • Sheets that have become wet during transport or storage should be dried; then, separate the sheets with spacers that allow for free air circulation. After drying, galvanized (aluzinc) sheets should be inspected and coated with a layer of preservative oil.
  • Sheets intended for long-term storage should be inspected and then coated with a layer of machine oil (applies to galvanized and aluzinc sheets) and, above all, protected from moisture (applies to all sheets).
  • Failure to follow the above recommendations results in the relatively rapid formation (for galvanized and aluzinc sheets, this can take as little as a few days) of zinc corrosion — that is, white layers loosely bonded to the substrate that do not provide protection against corrosion.
  • Coated sheets in their original factory packaging should not be stored for more than 3 weeks from the date of manufacture. After this time, the packaging must be opened, and the sheets must be separated with spacers that allow for free air circulation. The maximum storage period should not exceed 6 months from the date of manufacture, under penalty of voiding the Warranty.
  • Protective films are used to provide additional protection for coated metal sheets against mechanical damage, deformation, and impacts that may occur during transportation, handling, or forming. Protective films never exempt the user from the obligation to properly protect the sheets during storage or from the harmful effects of chemical agents during the processing. It is recommended to remove the film from the finished profiles gradually, piece by piece, shortly before installing the wall and roof components on the building.
  • Improper storage can make it difficult to remove the protective film and leave adhesive residue on the sheets.
Choose a coating:
More information about coatings
PS15glossy polyester

Technical specification of the coating

Coating thickness
15 µm (on both sides)
Information
A 15 µm thick polyester base coat applied to both sides. A custom coat color can be used as an additional layer. Please contact the technical department to discuss the details.

Available colours

RAL 9010
RAL 9010
The PRUSZYŃSKI company guarantees that each individual order will be fulfilled in the same colour (shade). However, due to the complexity of coating processes, differences in shades between individual deliveries may occur.

Responsibility for the colour is therefore limited to only one delivery.

Consequently, when reordering sheets for a specific batch, please indicate on the order or inform the Sales Representative that it is a continuation of an order and provide a colour sample.

To ensure the colour consistency of sandwich panels with other elements such as flashings, they should be ordered from a single supplier.

Product Description

The function of smoke curtains (along with other components) is to control the movement and/or accumulation of smoke and heat. Smoke curtains can contain smoke and gases with temperatures exceeding even 600°C, but they should not be confused with fire compartments. Smoke curtains are primarily designed to prevent the uncontrolled spread of smoke and fire gases in large-area spaces—such as warehouses, industrial halls, etc. Given their important role in the fire protection system, the facility designer should be responsible for selecting the curtains , ensuring they are suited to their specific application.

The T35KD fixed smoke curtains, manufactured by the Pruszyński Company from sheet metal, are a permanent component of the gravity smoke exhaust system and are coated on both sides with a protective polyester coating. The minimum steel grade used for the curtains is S280GD. The thickness of the sheet metal used for the smoke curtains is 0.60 mm. The sheet metal is coated on both sides with an organic polyester (SP) coating with a maximum thickness of 35 µm. The maximum height of the curtains is 450 cm.

The Blachy Pruszyński Company also offers flashings designed to fit T35 KD curtain walls. They are made from the same high-quality sheet metal as the curtain wall itself. The basic offering includes 4 flashings:

  • Comb Machining *
  • Finishing Flash (Roof Gap)
  • Closing flash (top gap)
  • Finishing (bottom gap)
Obróbka grzebieniowa do zaslepienia dachowej blachy trapezowej

Comb Machining

(It is mounted to the trapezoidal sheets used in the roof structure. Its dimensions depend on the trapezoidal sheets used in a given project )

Obrobka zamykajaca do zaslepienia szczeliny miedzy blacha trapezowa a blacha kurtyny


(roof gap) finishing

Obrobka zamykajaca mocowana u gory blachy kurtyny


(top gap) finishing

Obrobka zamykajaca mocowana u dolu blachy kurtyny


(roof gap) finishing

In addition to standard flashings, we also offer custom curtain flashings based on your design. To learn more about our offerings, please contact our sales department.

Additional technical schemes of the basic machining operations, along with detailed descriptions, can be found in the T35KD assembly manual: DOWNLOADS